Battery Backup Calculator — UPS / Inverter Runtime

Estimate UPS or inverter backup from battery-bank configuration, state of charge, capacity allowance and AC load.

ELECTRICAL TOPICBattery Backup Calculator

Your result

BACKUP ESTIMATEREADY
—Enter values below and press Calculate.
RESULT DISPLAYV × Ah → hours

Input values

ENTER YOUR EQUIPMENT DATA
100 = nominal capacity; use a justified lower allowance for the actual bank.
Do not count losses again if already included in entered efficiency.

Formula and worked example

Bank V = battery V × series count; bank Ah = battery Ah × parallel strings. Usable Wh = bank V × bank Ah × remaining-capacity fraction × (start SOC − minimum SOC) / 100. Hours = usable Wh / (AC watts / inverter efficiency + additional DC idle watts).

Worked example

Two 12 V batteries in series per string and two parallel strings, each battery 150 Ah, form a 24 V / 300 Ah bank. With 80% remaining-capacity allowance, SOC from 100% to 50%, 90% inverter efficiency, zero additional idle draw and 1,000 W AC load, estimated backup is 2.592 hours (155.52 minutes).

Using this tool

Enter the actual equipment and project values. The Use example button loads an illustrative case. Calculation happens in your browser; no Python, API key or account is required. Use the result details to see the inputs and scope, copy the result, download CSV or print.

Series में voltage बढ़ता है, Ah नहीं। Parallel strings से Ah बढ़ता है। यह energy estimate है; वास्तविक runtime के लिए battery/UPS discharge chart, cut-off और load conditions देखें।

Advertisement

Common questions

Is this guaranteed UPS runtime?

No. The energy model does not reproduce every battery discharge curve, temperature effect, Peukert effect, BMS/cut-off setting or inverter overload condition.

Can I add series battery Ah values?

A series string retains the Ah capacity of an individual equal battery while its voltage adds. Parallel equal strings add bank Ah.

Which load should I enter?

Enter the actual AC watts expected during backup, not UPS kVA or the sum of equipment labels without considering simultaneous use.

Related practical guides

Advertisement

Other calculators

Formula references and model scope

Formula review: 2 November 2026. Examples are illustrative. Enter project-specific data; a planning result does not certify an installation or equipment selection.

KEEP LEARNING WITH ELECTRICAL TOPIC

Learn Faster. Improve Your Electrical Skills.

Read practical guides on our website and subscribe to our Hindi technical YouTube channel. Learn testing, maintenance, troubleshooting and interview skills.

WEBSITE • EMAIL UPDATES

New guides. Straight to your inbox.

Subscribe free. Get fresh website updates.

Have a question? Email info@electricaltopic.com

Videos in Hindi

Electrical Topic on YouTube

Watch practical electrical lessons from our YouTube channel.

Visit channel